Rated Input Voltage: | 380/400/415VAC 3-phase 4-wire | Rated Frequency: | 50/60HZ |
---|---|---|---|
Input Voltage Range: | ±25% | Input Frequency Range: | 45Hz~65Hz |
Input Soft Start Function: | 0-100% 5-300settable | Input Power Factor: | >0.98(If Harmonic Filter Is Added) |
Bypass Voltage Range: | -20%~+15% | Bypass Frequency Range: | 50/60HZ±10% |
Highlight: | Pure Sine Wave UPS |
380V 1ph 2.9ln 300KVA / 270KW Low Frequency Online UPS LCD to provide electricity in theater or other place
Key Features:
1. On-Line Dual Conversion, fully isolating the influences of power grid pollution and power failure from utility power supply and diesel generator to load
2. Rated at 0.9 output power factor, more applicable to server computer and network center that use PFC technology in a large scale, and deliver more Active power than conventional UPS
3. Use advanced 6th generation DSP and full digital control technologies to realize higher system stability
4. Multi input harmonic suppressing technology improves the utility rate of electric Power Output isolation transformer with zero phase shift reduces the influences of Neutral to Ground voltage and load harmonic current to inverter
5. Extra strong capability to withstand output overload and short circuit, ensuring the system stability and system safety under extreme conditions
6. Advanced distributed active parallel technology can realize parallel operation of six UPS units without the need of centralized bypass cabinet
7. Extra wide input voltage and frequency range make it adapt to severe power grid environment
8. Standard input/output filter improves the system EMC performance
9.Intelligent battery management maintains battery automatically to prolong the battery life
10.6 inch extra large LCD that can display 12 language(Chinese.English.Russian.Spanish.French and so on)
11. Layered independently-sealed ventilation channel and redundant fan, circuit boards with protective paints and a dust filter embedded make it highly efficient to dissipate heat and protect the product effectively under severe environment.
Applications:
Mainly used in large IDC rooms, bank/securities settlement center, communication network management center, semiconductor product lines and large automation production and its control system. According to the special needs of users was improved, and used in large sports venues, conference room, theater and highway and railway tunnels metal halide lamp lighting system.
Technical Specifications of Online UPS GP9335C 120-800KVA
Model |
GP9335C |
|||||||||||
Rectifier Type |
6p |
12p |
6p |
12p |
6p |
12p |
6p |
12p |
6p |
12p |
||
Rated Nominal |
120KVA/108KW |
160KVA/144KVA |
200KVA/180KW |
300KVA/270KW |
400KVA/36W |
|||||||
Rated input voltage |
380/400/415VAC 3-phase 4-wire |
|||||||||||
Rated frequency |
50/60HZ |
|||||||||||
Input parameters |
||||||||||||
Input voltage range |
±25% |
|||||||||||
Input frequency range |
45Hz~65Hz |
|||||||||||
Input soft start function |
0-100% 5-300settable |
|||||||||||
Input power factor |
>0.98(If harmonic filter is added) |
|||||||||||
Input harmonic current (THDi) |
<4.5%(If harmonic filter is added) |
|||||||||||
Bypass |
||||||||||||
Bypass voltage range |
-20%~+15% |
|||||||||||
Bypass frequency range |
50/60HZ±10% |
|||||||||||
Output parameters |
||||||||||||
Inverter output voltage |
380/400/415VAC 3-phase 4-wire |
|||||||||||
Voltage stability |
±1%(Steady status), ±3%(Transient status) |
|||||||||||
Frequency |
50/60Hz |
|||||||||||
Mains power synchronization window |
±5% |
|||||||||||
Actually measured frequency accuracy (internal clock) |
50/60Hz±0.01Hz |
|||||||||||
Output power factor |
0.9(Output 90kW per 100kVA) |
|||||||||||
Transient response time |
<5ms |
|||||||||||
Inverter overload capability |
At 0.9 power factor, 110% for 1 hour, 125% for 10 minutes and 150% for 60s |
|||||||||||
Short circuit current from inverter |
3ph 1.5ln for 5seconds, 1ph 2.9ln for 5seconds |
|||||||||||
Maximum Bypass capability |
1000% for 100ms |
|||||||||||
Phase shift |
With 100% balanced load |
<1° |
||||||||||
With 100% imbalance load |
<1° |
|||||||||||
Total harmonic |
100% linear load |
<1% |
||||||||||
100% non-linear load |
<3% |
|||||||||||
System efficiency (full load) |
Up to 94% (inverter efficiency is up to 98%) |
|||||||||||
Rectifier output parameters |
||||||||||||
Charger output voltage stability |
1% |
|||||||||||
DC ripple voltage |
≤1% |
|||||||||||
Operating environment |
||||||||||||
Operating temperature range |
0~40℃ |
|||||||||||
Storage temperature |
-25~70℃(Without battery) |
|||||||||||
Relative humidity |
0~95% No condensation |
|||||||||||
Maximum operating height |
≤Elevation 1000m, for elevation above 1000m, derate by 1% for every increase of 100m |
|||||||||||
Noise (1m) |
58-68dB |
|||||||||||
Protection level |
IP20 |
|||||||||||
Standard |
Safety: IEC60950-1 IEC62040-1-1 UL1778 EMC IEC62040-2 CLASS C2 EN50091-2 CLASS A Design and Test IEC62040-3 |
|||||||||||
Physical parameters |
||||||||||||
Weight (kg) |
980 |
1420 |
1200 |
1750 |
1350 |
2000 |
1600 |
2200 |
2100 |
2750 |
||
Width(mm) |
900 |
1250 |
1250 |
1640 |
1250 |
1640 |
1640 |
2280 |
2280 |
2280 |
||
Depth (mm) |
855 |
855 |
855 |
855 |
855 |
855 |
855 |
855 |
855 |
855 |
||
Height (mm) |
1900 |
1900 |
1900 |
1900 |
1900 |
1900 |
1900 |
1900 |
1900 |
1900 |
Follow standard of GB/IEC regulation: EMC:GB7260.2/IEC62040-2 GB/17626.2~5/IEC61000-4-2~5 SAFETY:GB4943
Note: Product specifications are subject to change without further notice
Contact Person: Mr. Song
Tel: 86-137367899
Fax: 86-755-7287468
Single Phase / Three Phase Power Supply Online UPS for Communication System
Intelligent AC to DC Integrated Power Supply Online UPS High Frequency and Single Phase
Custom Three Phase Online UPS / 3 phase UPS Low Frequency for Network or Highway lighting
china Solar LED Street Light manufacturer
Solar Powered Street Lights 50 Watt | Integrated Series
IP 65 3000K 4000K Solar LED Street Lights Photovoltaic , Bright Solar Lights
High Power Low Frequency Online UPS IP20 DSP Control For Industrial
Low Frequency Online UPS With Touch Screen Function 10-200KVA
3Phase Low Frequency Online UPS With Isolation Transformer Inside